天津科学技术出版社

故障分量驱动下配电线路保护灵敏度的提升

王子月
作者信息
  1.  国网江苏省电力有限公司扬州供电分公司  江苏 扬州  225000

摘要

配电线路运行方式变化频繁,分布式电源接入后,故障电流幅值和方向更易受潮流状态影响,传统工频全量保护在高阻故障、弱馈入场景下容易出现灵敏度不足。本文围绕故障分量的形成机理、提取方法和动作判据展开研究,分析过渡电阻、运行方式变化以及分布式电源接入对保护灵敏度的影响,提出基于自适应启动门槛、状态感知整定、多电气量融合和高阻故障连续识别的优化方法。通过建立含逆变型光伏电源的10 kV配电线路仿真模型,对不同故障位置、过渡电阻、负荷水平以及分布式电源运行状态下的保护性能进行验证。结果表明,改进方法能够有效降低负荷变化和故障电流衰减对保护动作的影响,在500 Ω高阻接地故障条件下仍保持较高灵敏系数,同时具备区外故障方向制动能力,可提升复杂运行环境下配电线路继电保护的可靠性。

Improvement of Distribution Line Protection Sensitivity Driven by Fault Components

Ziyue Wang
Author Information
  1.  Yangzhou Power Supply Branch, State Grid Jiangsu Electric Power Co., Ltd., Yangzhou 225000, Jiangsu Province, China

Abstract

Distribution lines frequently change their operating modes. After the integration of distributed generation, the amplitude and direction of fault currents are more susceptible to power flow states, making traditional power-frequency full-quantity protection prone to insufficient sensitivity under high-resistance faults and weak-infeed scenarios. This paper investigates the formation mechanism, extraction methods, and operating criteria of fault components, analyzes the effects of transition resistance, operating mode changes, and distributed generation integration on protection sensitivity, and proposes optimization methods based on adaptive starting thresholds, state-aware setting, multi-electrical-quantity fusion, and continuous identification of high-resistance faults. By establishing a simulation model of a 10 kV distribution line containing inverter-based photovoltaic sources, the protection performance is verified under different fault locations,transition resistances, load levels, and distributed generation operating states. The results show that the improved method can effectively reduce the impact of load variations and fault current attenuation on protection operation, maintain a high sensitivity coefficient under 500 Ω high-resistance grounding fault conditions, and possess directional blocking capability for out-of-zone faults, thereby enhancing the reliability of distribution line relay protection in complex operating environments.